Designed for maintenance and repair teams and operators personnel that needs a reliable, fast and easy to use tool for basic condition monitoring in rough conditions. VIBER X2¢â measures Bearing Condition and vibration in accordance with ISO-standards. VIBER X2¢â has an extrenal sensor with 1 meter cable. This makes the readings more reliable and much safer for the user compared to instruments with cheaper embedded sensors.
• Real-time measurements of the total vibration level and the Bearing Condition (BC),shown simultaneously
• Bar indicator displays measurement stability
• Fast and easy fault analysis displaying the five largest amplitude peaks frequency in RPM or Hz on main screen display
• Low power consumption
• Overflow alarm limits are clearly displayed with a yellow and red LED indicator
• Several languages are available
• Dust and waterproof, for rough use (IP 65)
|
|
|
|
|
|
|
|
Viber X2¢â
Vibration transducer
|
Accelerometer
|
Standard nom 100 mV/g
|
(Selectable sensitivity in the instrument)
|
0,1 - 99999 mV/g
|
Input amplitude range
|
Vibration
|
Max 50g RMS
|
With other sensor up to 500g and
|
down to 0,05g
|
Bearing condition
|
Max 20g
|
|
Dynamic range
|
80 dB (at 159 Hz with auto ranging)
|
|
Frequency range
|
Vibration
|
2 - 400 Hz
|
User selectable
|
10 - 1000 Hz
|
6 - 1600 Hz
|
11 - 3200 Hz
|
Bearing condition
|
0.5 to 16 kHz
|
|
Vibration units
|
g-value, mm/s, m/s2, in/s, µm, mils
|
User selectable
|
Amplitude presentation
|
RMS, Peak, Peak-Peak
|
User selectable
|
Analysis
|
Five highest peaks can be displayed
|
|
|
Frequency range
|
|
Frequency range of peak
|
2 - 400 Hz
|
|
detection
|
6 - 1600 Hz
|
User selectable unit, between Hz and RPM
|
|
11 - 2000 Hz
|
|
|
10 - 1000 Hz
|
|
Accuracy
|
Vibration
|
¡¾ 3 %
|
Full scale is 50g for acceleration
|
other units are frequency dependent
|
All values are related to the
|
normal acceleration 9,80665 m/s2
|
Bearing condition
|
¡¾ 5 %
|
Over 0,05 gBC
|
Frequency/RPM
|
¡¾ 0.2 %
|
|
Battery
|
Rechargeable Lithium
|
2300 mA/h max 60¢ª
|
Capacity of the batteries can
|
vary depending on hardware revision
|
Max 2300 mA/h
|
(Storage temp. -20¡ÆC to max 60¡ÆC)
|
Operating time
|
1 week normal use
|
|
External charger
|
5,0 V relugated @ 2000 mA
|
|
LCD display
|
B&W 64 x 120 pixels with
|
Operating temp. min 0¡ÆC to max 50¡ÆC
|
background light
|
storage temp. max 72¡ÆC
|
Enclosure protection
|
IP 65
|
|
Operating temp. range
|
0 to 50¡ÆC
|
The restriction concerns display
|
Weight
|
340 gram
|
Instrument, including battery and
|
transducer
|
Size (L x W x H)
|
145mm x 77mm x 47mm
|
|
|
|
|
| |
|